TECHNICAL DATA / DEVICE SELECTION
SD-2001Datasheet
EN 14604-certified optical smoke alarm with LoRaWAN event reporting and a built-in non-replaceable battery with an 8–10-year stated operational lifetime.

- Detection
- Optical smoke sensor
- Power
- Built-in battery
- Operational lifetime
- 8–10 years
- Connectivity
- LoRaWAN
Product overview
The YOBIIQ SD2001 is a battery-powered optical smoke detector and audible smoke alarm with built-in LoRaWAN communication. Its optical sensor is designed to detect smoke from slow, smouldering fires, while LoRaWAN reports detector events to a monitoring application.
The SD2001 is powered by a built-in non-replaceable, non-rechargeable battery. Its stated operational lifetime is 8–10 years, depending on environmental conditions. Plan replacement and maintenance in accordance with the supplied product documentation and applicable local requirements.
The smoke chamber, integrated insect screen and automatic dust compensation are designed to reduce nuisance alarms. Suitable locations may include living rooms, bedrooms, hallways, landings and dining rooms, subject to approved installation instructions and local siting rules. The SD2001 is stated to meet EN 14604 and Grade F1 under BS 5839-6.
Why choose SD-2001?
| Capability | Benefit |
|---|---|
| Optical smoke detection | Detect smoke from slow, smouldering fires in suitable residential locations. |
| Insect screen and dust compensation | Help reduce nuisance alarms caused by insects and dust accumulation. |
| LoRaWAN event reporting | Send recorded detector events and supported status information to a monitoring application. |
| Built-in long-life battery | Install without a mains connection or routine battery replacement; stated operational life is 8–10 years, depending on environmental conditions. |
| Test and hush button | Test locally, hush a smoke alarm for 10 minutes, or hush low-battery warning beeps for 10 minutes. |
| Wired interlink | Connect compatible YOBIIQ smoke alarms into a wired alarm group. |
| SD2001-RF wireless interlink | Group compatible YOBIIQ RF smoke alarms without a wired interlink. |
| SD2001-TH environmental sensing | Add temperature and humidity sensing for environmental monitoring. |
| SD-REMOTE accessory | Test and configure compatible wireless alarms from floor level, reducing ladder use during setup. |
The SD2001-TH is a smoke detector, not a heat detector as defined under EN 54-5 or BS 5446-2. Its temperature and humidity sensor is for environmental monitoring only. Temperature does not trigger the smoke alarm.
Applications
| Application | Example uses |
|---|---|
| Homes and apartments | Install in suitable living rooms, bedrooms, hallways, landings and dining rooms, following approved siting guidance. |
| Multi-apartment buildings | Interlink compatible detectors so alarms can be shared across a group. |
| Holiday and vacation homes | Monitor reported detector events remotely over LoRaWAN. |
| Residential property portfolios | Review detector events across apartments and managed homes where network coverage is available. |
| Installation and maintenance teams | Use local test and hush controls or SD-REMOTE to configure and test compatible RF detectors from floor level. |
LoRaWAN reporting and remote testing complement, but do not replace, the local audible alarm, required inspections or maintenance. Check network coverage, interlink compatibility and local installation requirements for each property.
Electrical specifications
| Parameter | Value |
|---|---|
| Power supply | Built-in non-replaceable, non-rechargeable battery |
| Stated operational lifetime | 8–10 years, depending on environmental conditions |
| Standby power consumption | Less than 0.2 W; |
| Audible alarm | Minimum 85 dB(A) at 3 m; confirm against the SD2001 variant documentation |
| Local controls | Test button; smoke-alarm hush and low-battery warning hush, each for 10 minutes |
Communication and configuration
| Parameter | Specification |
|---|---|
| LoRaWAN version | 1.0.4 |
| Device class | Class A |
| Activation | OTAA |
| Radio regions | EU868, IN865 |
| Maximum transmit power | 14 dBm at 868 MHz, 23 dBm at 865 MHz |
| LoRa antenna | Built-in; external SMA option |
| Local wireless interface | BLE with password authentication |
| Mobile configuration | Kibi Mobile App |
| Device-to-device communication | YOBIIQ D2D |
| Automation | Onboard schedules, event-driven and threshold logic |
| Network security | LoRaWAN AES-128 encryption and OTAA activation |
Integrate with ChirpStack, The Things Network, LORIOT or a private LoRaWAN network server. Match the radio region, device profile and payload decoder to the installed unit.
Test / Hush Button
| Parameter | Value |
|---|---|
| Event handling | Events are recorded in the detector and communicated over LoRaWAN |
| Testing and hush | Local test; smoke alarm hush and low-battery warning hush, each for 10 minutes |
Mechanical and environmental specifications
| Parameter | Value |
|---|---|
| Enclosure dimensions | 120 mm diameter; confirm against the supplied SD2001 documentation |
| Enclosure material / colour | PC UL94-V0 / white; confirm against the supplied SD2001 documentation |
| Enclosure protection | IP20; confirm against the supplied SD2001 documentation |
| Approximate weight | 102 g; confirm against the supplied SD2001 documentation |
Use the supplied installation instructions for siting, environmental limits and maintenance. Battery lifetime depends on environmental conditions and operating profile.
Variants
| Model | Description | SKU |
|---|---|---|
| SD2001 | Battery-powered smoke detector | 250103 |
| SD2001-RF | Battery-powered smoke detector with radio interlink | 250104 |
| SD2001-TH | Battery-powered smoke detector with temperature and humidity sensor | 250105 |
| SD-REMOTE | Remote for configuring smoke detectors | 250041 |
SD-REMOTE is an accessory rather than a smoke detector variant. Confirm model-specific ordering codes, interlink compatibility and sensor options before ordering.
Certifications & Compliance
| Certification / Compliance | Details |
|---|---|
| Electromagnetic Compatibility | EMC 2014/30/EU (SS-EN 55032:2015, SS-EN IEC 61000-6-1, -2, -3, -4) |
| Electrical Safety | LVD 2014/35/EU (IEC 62368-1:2018) |
| Radio | RED 2014/53/EU (EN 300 220-1, EN 300 220-2, EN 301 489-1, EN 301 489-3) |
| RoHS | RoHS 2002/95/EG |
| Smoke alarm product standard | EN14604:2005/AC:2008 |
| Domestic alarm-system grade | Grade D1 under BS 5836-6 |
| HS Code | 8531 10 30 |
| Country of Origin | China |
Confirm the applicable declaration and certificate for the supplied version before release. Compliance references must be checked against the specific SD2001 variant.