TECHNICAL DATA / DEVICE SELECTION
DEM2Datasheet
Single-phase direct energy metering up to 80 A, with a choice of LoRaWAN or Modbus RTU.

- Phases
- Single-phase
- Direct current
- 80 A
- Mounting
- DIN rail
- Communication
- LoRaWAN / Modbus RTU
Product overview
The YOBIIQ DEM2 combines single-phase direct metering up to 80 A with a choice of connection and I/O options. Select a version with two digital outputs, or one digital input and an integrated relay. LoRaWAN and Modbus RTU variants let you match the meter to the site’s communications infrastructure.
Use the meter to record demand and consumption at individual measurement points, so building and energy teams can compare operating periods and investigate unexpected use.
Why choose DEM2?
| Capability | Benefit |
|---|---|
| Single-phase direct measurement | Meter a circuit without external current transformers. |
| Demand measurement | Add demand information to the energy-consumption record. |
| LoRaWAN or Modbus RTU | Choose wireless or wired reporting when ordering. |
| DIN-rail mounting | Integrate the meter into a distribution board. |
| Model-specific I/O | Select the connections needed for the installation. |
Applications
| Application | Example uses |
|---|---|
| Buildings | Measure selected single-phase circuits in offices and shared spaces. |
| Equipment monitoring | Compare energy use across equipment operating periods. |
| Energy projects | Establish a baseline and assess the effect of operational changes. |
Digital output and relay functions
The DEM2 is available with two digital I/O configurations, selected by the model suffix.
On 2O models, the meter has two digital outputs. Regulations required under the MID certification reserve the first output as a fixed S0 pulse output, used for verified consumption reporting to a separate metering or billing system. The second output is configurable and can switch based on consumption, voltage or current thresholds, making it suitable for a range of applications such as timer-based controls or prepaid/postpaid billing in combination with an external relay.
On 1I1R models, the meter has one digital input and one integrated relay in place of the second digital output. The digital input can register an external contact or event, and the integrated relay can switch directly, without requiring an external relay.
Digital output and relay use cases
| Use case | Description |
|---|---|
| Prepaid or postpaid billing | Use the configurable output (2O) or integrated relay (1I1R) to enable or disable supply based on prepaid credit or postpaid billing status. |
| Timer-based load control | Switch connected equipment on or off according to a configured schedule. |
| Remote load shedding | Drive a contactor or relay command to remove non-critical loads during demand peaks and avoid penalty costs. |
| Alarm beacon activation | Trigger visual or audible alarms when thresholds are crossed, making abnormal power behavior immediately visible on-site. |
| Controlled reconnect workflow | Support supervised remote reconnect procedures after validation checks in rental, tenant or temporary service scenarios. |
| Run/stop signal to auxiliary device | Send a simple control signal to ventilation, pump or process support equipment based on metering logic. |
| Tariff contact logging (1I1R) | Capture utility tariff state changes or external pulse contact events to correlate rate periods with measured consumption. |
| Breaker status feedback (1I1R) | Read an auxiliary breaker contact to confirm trip/open state and improve electrical incident visibility for maintenance teams. |
| Generator transfer state (1I1R) | Track ATS or generator run-state signals for runtime analysis, emergency readiness and post-event reporting. |
| Door / panel tamper event (1I1R) | Use a dry contact to register enclosure access and add a security audit trail to remote electrical rooms. |
| Closed-loop edge automation (1I1R) | Use the digital input as permissive feedback and the integrated relay as actuation to build a straightforward local control loop with central visibility. |
Communication and configuration
| Parameter | Specification |
|---|---|
| LoRaWAN version | 1.0.4 |
| Device class | Class C by default; configurable to Class A |
| Activation | OTAA |
| Radio regions | EU868, IN865 |
| Maximum transmit power | 14 dBm at 868 MHz, 23 dBm at 865 MHz |
| LoRa antenna | Built-in; external SMA option |
| Local wireless interface | BLE with password authentication |
| Mobile configuration | Kibi Mobile App |
| Device-to-device communication | YOBIIQ D2D |
| Automation | Onboard schedules, event-driven and threshold logic |
| Network security | LoRaWAN AES-128 encryption and OTAA activation |
Integrate with ChirpStack, The Things Network, LORIOT or a private LoRaWAN network server. Match the radio region, device profile and DEM payload decoder to the installed unit.
Electrical specifications
| Parameter | Value |
|---|---|
| Phases | Single-phase |
| Current connection | Direct |
| Maximum direct current | 80 A |
| Demand measurement | Supported |
| Measurment Accuracy | Class B |
| Digital outputs | 2 on 2O models |
| Digital inputs | 1 on 1I1R models; none on 2O models |
| Integrated relay | 1 on 1I1R models; none on 2O models |
Variants
| Model | Direct current | Digital outputs | Digital inputs | Relays | Communication |
|---|---|---|---|---|---|
| DEM2-80-2O-L | 80 A | 2 | 0 | 0 | LoRaWAN |
| DEM2-80-2O-M | 80 A | 2 | 0 | 0 | Modbus RTU |
| DEM2-80-1I1R-L | 80 A | 0 | 1 | 1 | LoRaWAN |
| DEM2-80-1I1R-M | 80 A | 0 | 1 | 1 | Modbus RTU |
The L and M variants are alternative communication configurations. Order by the complete model code and confirm the radio region for a LoRaWAN unit.
Communication and configuration
| Variant suffix | Interface |
|---|---|
| L | LoRaWAN |
| M | Modbus RTU |
Mechanical and environmental specifications
| Parameter | Value |
|---|---|
| Enclosure dimensions | 90 × 36 mm (height × width) |
| Width | Two DIN modules |
| Mounting | TS35 DIN rail |
| Enclosure material / colour | ABS UL94-V0 / green |
| Enclosure protection | IP20 |
| Approximate weight | 150 g |
| Operating temperature | −30°C to +55°C |
| Storage temperature | −40°C to +85°C |
| Operating humidity | 0–85% RH, non-condensing |
Enclosure dimensions, protection rating and environmental limits require the model-specific specification before installation planning.
Certifications & Compliance
| Certification / Compliance | Details |
|---|---|
| Electromagnetic Compatibility | EMC 2014/30/EU (SS-EN 55032:2015, SS-EN IEC 61000-6-1, -2, -3, -4) |
| Electrical Safety | LVD 2014/35/EU (IEC 62368-1:2018) |
| Radio | RED 2014/53/EU (EN 300 220-1, EN 300 220-2, EN 301 489-1, EN 301 489-3) |
| RoHS | RoHS 2002/95/EG |
| MID | Module B + D |
| HS Code | 9028 30 00 |
| Country of Origin | Turkey |
Related documentation